Chapter 14 Fault CodesMH300
14-64
ID No.
Display Fault Name Description
62
Deceleration energy
backup fault
(dEb)
When Pr. 07-
13 is not 0, and the power is suddenly
off, causing the DC bus voltage lower than the dEb
action level, the dEb function acts and the motor
ramps to stop. Then dEb displays on the keypad.
Action and Reset
Action condition
When Pr. 07-
13 is not 0, and the DC bus voltage is lower than the level of
dEb.
Action time Act immediately
Fault treatment parameter N/A
Reset method
Auto
When Pr. 07-13=2 (dEb with auto-acceleration / auto-
deceleration, the drive outputs the frequency after the power is
restored): dEb is automatically cleared.
Hand
When Pr. 07-13=1 (dEb with auto-acceleration / auto-
deceleration, the drive does not output the frequency after the
power is restored): The drive stops when dEb acts and the
rotation speed becomes 0 Hz, then the drive can be reset
manually.
Reset condition
Auto: The fault is automatically cleared.
Hand: When the drive decelerates to 0 Hz.
Record Yes
Cause Corrective Actions
Unstable power source or the
power is off
Check the power system.
There is any other large load
operates in the power system
1. Replace power system with a larger capacity.
2. Use a different power system from the large load system.