Chapter 14 Fault CodesMH300
ID No.
Display Fault Name Description
144
Auto-tune error 3
(AUE3)
No load current I
0
measurement error when motor
parameter automatically detects.
Action and Reset
Action condition Software detection
Action time Immediately act
Fault treatment parameter N/A
Reset method Manual reset
Reset condition Immediately reset
Record Yes
Cause Corrective Actions
Incorrect settings for the motor
parameter (rated current)
Check the settings for Pr.05-01 / Pr.05-13 / Pr.05-34.
Motor error Check if the motor works normally.