EasyManua.ls Logo

GE Feeder Management Relay 750 - Page 125

GE Feeder Management Relay 750
346 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GE Multilin 750/760 Feeder Management Relay 5-61
5 SETPOINTS 5.6 S5 PROTECTION
5
The setpoints for Negative Sequence Directional are described below.
NEG SEQ DIRECTIONAL MTA: Enter the maximum torque angle by which the operating current leads the polarizing
voltage. This is the angle of maximum sensitivity.
MIN POLARIZING VOLTAGE: As the system negative sequence voltage is used as the polarizing voltage for this ele-
ment, a minimum level of voltage must be selected to prevent operation caused by system unbalanced voltages or VT
ratio errors. For well-balanced systems and 1% accuracy VTs, this setpoint can be as low as 2% of VT nominal volt-
age. For systems with high-resistance grounding or floating neutrals, this setpoint can be as high as 20%. The default
value of "0.05 x VT" is appropriate for most solidly grounded systems.
Figure 5–25: NEGATIVE SEQUENCE DIRECTIONAL LOGIC
Table 5–15: NEGATIVE SEQUENCE DIRECTIONAL CHARACTERISTICS
QUANTITY OPERATING CURRENT POLARIZING VOLTAGE
Negative Sequence (ABC phase sequence)
Negative Sequence (ACB phase sequence)
I
a2
I
a
a
2
I
b
aI
c
++
3
-----------------------------------= V
a2
V
a
a
2
V
b
aV
c
++
3
------------------------------------------=
I
a2
I
a
aI
b
a
2
I
c
++
3
-----------------------------------= V
a2
V
a
aV
b
a
2
V
c
++
3
------------------------------------------=
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals