GE Multilin 750/760 Feeder Management Relay 5-95
5 SETPOINTS 5.7 S6 MONITORING
5
5.7.9 PULSE OUTPUT
PATH: SETPOINTS ÖØ S6 MONITORING ÖØ PULSED OUTPUT
The 750/760 can operate selected auxiliary relays after an adjustable interval for the quantities shown above. Pulses occur
at the end of each programmed interval. Upon power up of the relay the Pulse Output function, if enabled, will continue
from where it was at loss of control power. For example, if control power is removed when the positive watthours actual
value is 16.0 MWh, when control power is re-applied a pulse will occur at 26 MWh if the interval is set to 10.0 MWh.
Note that the Output relay(s) used for this element must be set to "Self-Resetting" under
S4 OUTPUT RELAYS. The pulses will
consist of a one second on time and a one second off time. This feature should be programmed such that no more than one
pulse per two seconds will be required or the pulsing will lag behind the interval activation.
Figure 5–56: PULSED OUTPUT LOGIC
îš„ PULSED OUTPUT
îš„ [ENTER] for more
PULSED OUTPUT
FUNCTION: Disabled
Range: Disabled, Alarm, Latched Alarm, Control
POS WATTHOURS PULSED
RELAYS (3-7): -----
Range: Any combination of 3 to 7 Auxiliary relays
POS WATTHOURS PULSED
INTERVAL: 10.0 MWh
Range: 0.0 to 6553.5 MWh in steps of 0.1.
Quantities auto-range to appropriate units.
NEG WATTHOURS PULSED
RELAYS (3-7): -----
Range: Any combination of 3 to 7 Auxiliary relays
NEG WATTHOURS PULSED
INTERVAL: 10.0 MWh
Range: 0.0 to 6553.5 MWh in steps of 0.1.
Quantities auto-range to appropriate units.
POS VARHOURS PULSED
RELAYS (3-7): -----
Range: Any combination of 3 to 7 Auxiliary relays
POS VARHOURS PULSED
INTERVAL: 10.0 Mvarh
Range: 0.0 to 6553.5 Mvarh in steps of 0.1.
Quantities auto-range to appropriate units.
NEG VARHOURS PULSED
RELAYS (3-7): -----
Range: Any combination of 3 to 7 Auxiliary relays
NEG VARHOURS PULSED
INTERVAL: 10.0 Mvarh
Range: 0.0 to 6553.5 Mvarh in steps of 0.1.
Quantities auto-range to appropriate units.
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
Courtesy of NationalSwitchgear.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Feeder Management Relay 750 and is the answer not in the manual?

GE Feeder Management Relay 750 Specifications

General IconGeneral
BrandGE
ModelFeeder Management Relay 750
CategoryProtection Device
LanguageEnglish

Related product manuals