5-122 750/760 Feeder Management Relay GE Multilin
5.8 S7 CONTROL 5 SETPOINTS
5
c) AUTORECLOSE RATE SUPERVISION
PATH: SETPOINTS ÖØ S7 CONTROL ÖØ AR ÖØ RATE SUPERVISION
The autoreclose rate supervision feature monitors the number of recloses per hour. Once the number of recloses within
one hour exceeds the
MAX AR RATE setpoint, the autoreclose scheme is sent to lockout.
Figure 5–74: AUTORECLOSE RATE SUPERVISION LOGIC
d) AUTORECLOSE CURRENT SUPERVISION
PATH: SETPOINTS ÖØ S7 CONTROL ÖØ AR ÖØ CURRENT SUPERVISION
RATE SUPERVISION
[ENTER] for more
RATE SUPERVISION
FUNCTION: Disabled
Range: Disabled, Alarm, Latched Alarm, Control
RATE SUPERVISION
RELAYS (3-7): -----
Range: Any combination of the 3 to 7 Auxiliary relays
MAX AR
RATE: 25 /hr.
Range: 1 to 50/hr. in steps of 1
CURRENT SUPERVISION
[ENTER] for more
CURRENT SUPERVISION
FUNCTION: Disabled
Range: Enabled, Disabled
3 SHOTS FOR CURRENT
ABOVE: 17.00 x CT
Range: 0.00 to 20.00 x CT in steps of 0.01
2 SHOTS FOR CURRENT
ABOVE: 18.00 x CT
Range: 0.00 to 20.00 x CT in steps of 0.01
1 SHOTS FOR CURRENT
ABOVE: 19.00 x CT
Range: 0.00 to 20.00 x CT in steps of 0.01
CURRENT SUPERVISION
TO LOCKOUT: Disabled
Range: Enabled, Disabled
LOCKOUT FOR CURRENT
ABOVE: 20.00 x CT
Range: 0.00 to 20.00 x CT in steps of 0.01
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE