8-46 750/760 Feeder Management Relay GE Multilin
8.6 CONTROL SCHEMES 8 COMMISSIONING TESTS
8
The following procedure checks Minimum Voltage with Three Phases For Operation:
1. Assert or De-assert a logic input to simulate an open breaker.
2. Set
UNDERVOLT RESTORE DELAY to "0".
3. Inject V
an
= V
bn
= V
cn
= nominal voltage into the bus voltage input of the relay.
4. Reduce the injected voltages to cause an undervoltage trip, then set V
an
and V
cn
to nominal.
5. Slowly raise V
an
until the Close Relay operates. This is the operating level of UNDERVOLT RESTORE MIN VOLTS for V
an
.
6. Inject V
an
= V
bn
= V
cn
= nominal voltage into the bus voltage input of the relay.
7. Reduce the injected voltages to cause an undervoltage trip, then set V
an
and V
cn
to nominal.
8. Slowly raise V
bn
until the Close Relay operates. This is the operating level of UNDERVOLT RESTORE MIN VOLTS for V
bn
.
9. Inject V
an
= V
bn
= V
cn
= nominal voltage into the bus voltage input of the relay.
10. Reduce the injected voltages to cause an undervoltage trip, then set V
an
and V
bn
to nominal.
11. Slowly raise V
cn
until the Close Relay operates. This is the operating level of UNDERVOLT RESTORE MIN VOLTS for V
cn
.
b) FOR DELTA VTS
Make the test connections specified in Figure 8–2: Relay Test Wiring – Delta Connection on page 8–3. The following proce-
dure checks Minimum Voltage with One Phase For Operation:
1. Assert or De-assert a logic input to simulate an open breaker.
2. Set UNDERVOLT RESTORE DELAY to 0.
3. Inject V
ab
= V
cb
= nominal voltage into the bus voltage input of the relay.
4. Reduce the injected voltages to cause an undervoltage trip, then set V
cb
to 0 V.
5. Slowly raise V
ab
until the Close Relay operates. This is the operating level of UNDERVOLT RESTORE MIN VOLTS for V
ab
.
6. Repeat Steps 3 through 5 except adjust V
cb
.
The following procedure checks Pickup with Two or Three Phases For Operation:
1. Assert or De-assert a logic input to simulate an open breaker.
2. Set
UNDERVOLT RESTORE DELAY to 0.
3. Inject V
ab
= V
cb
= nominal voltage into the bus voltage input of the relay.
4. Reduce the injected voltages to cause an undervoltage trip, then set V
cb
to nominal.
5. Slowly raise V
ab
until the Close Relay operates. This is the operating level of UNDERVOLT RESTORE MIN VOLTS for V
ab
.
6. Inject V
ab
= V
cb
= nominal voltage into the bus voltage input of the relay.
7. Reduce the injected voltages to cause an undervoltage trip, then set V
ab
to nominal.
8. Slowly raise V
cb
until the Close Relay operates. This is the operating level of UNDERVOLT RESTORE MIN VOLTS for V
cb
.
8.6.6 UNDERFREQUENCY RESTORATION
Make the test connections specified in Figure 8–1: Relay Test Wiring – Wye Connection or Figure 8–2: Relay Test Wiring –
Delta Connection on page 8–3. The following procedure checks Logic and Timers for Underfrequency Restoration:
1. Program the
UNDERFREQ 1 FUNCTION as “Trip”, MIN VOLTAGE as “0”, and UNDERFREQ 2 FUNCTION as “Disabled”.
2. Assert or De-assert a logic input to simulate a closed breaker.
3. Inject a voltage at nominal voltage and frequency into the bus voltage Phase A input.
4. Initially set
UNDERFREQ RESTORATION setpoint to Alarm, and other setpoints as required.
5. Reduce the frequency to below the underfrequency pickup level. After the programmed delay Underfrequency 1
should cause a trip, which should not initiate underfrequency restoration as the breaker is closed. Diagnostic message
"Ufreq Restore Init" should not be displayed.
Courtesy of NationalSwitchgear.com