8. Wait about three minutes, and then confirm that Power LED and Status
LED of the FC switch module emit in green.
9. Press Enter key to display login prompt of FC switch module.
10. Enter admin as login name, and then press Enter key.
11. Enter password as password, and then press Enter key.
12. Enter ag --modeshow, and then press Enter key.
Confirm that a message "Access Gateway mode is enabled." is
indicated.
13. Skip from this step 13 when the switch monitor mode of failed FC switch
was Fabric mode.
Enter mapsconfig --enablemaps -policy dflt_conservative_policy,
and then press Enter key to set MAPS mode.
Enter y when "Do you want to continue? (yes, y, no, n): [no]" is
indicated, and then press Enter key.
Common process for replacement
4-29
Hitachi Compute Blade 500 Series System Service Manual