20. Verify that the power LED lights in green after blinking, and that the
primary LED is off.
21. Restarting the installed management module.
Select Resources tab on the web console and select Modules > All
Modules > Management Modules.
Confirm that the status of installed management module number which
status is indicated as Standby in the Hot standby status column in the
lower right pane.
Figure 5-135 Confirm the installed management module number
22. Click the Installed (Standby) management module.
23. Click Action and select Restart.
24. The confirmation dialog box appears. Click OK.
Figure 5-136 Restarting the installed management module
25. About five minutes later, the management module will reboot.
Replacing parts
5-105
Hitachi Compute Blade 500 Series System Service Manual