5 To return to the test run menu press “ ” (return) while indoor unit is not operated.
Conrm the selected indoor unit address and go to “I.U. Address Change”.
NOTE
“ADD Check Operation” is not available when the control of 2 remote control switches (main and sub) are used.
The switch operation other than “Run/Stop” is not available while “ADD Check Operation” is performed.
Do not operate from the central controlling devices while “ADD Check Operation” is performed by the remote control switch.
This function should not be used if there is a Central Control (like CSNET WEB) in the H-LINK line.
Indoor Unit Address Initialization
This function initializes the indoor unit address that has been changed by “I.U. Address Change” function or set by the au-
tomatic address allocation. Initializing the address by this function, indoor unit address is changed to the dip switch setting.
1 Press and hold “
” (menu) and “ ” (return) simultaneously for at
least 3 seconds during the normal mode (when unit is not oper-
ated). The test run menu is displayed then.
2 Select “I.U. ADD Initialization” from the test run menu pressing
” and “OK”.
3 Select the indoor unit by pressing “
” and press “OK”,
then the conrmation screen is displayed.
*Indoor units which are not supporting “I.U. ADD Initialization” func-
tion can not be selected.
The address of indoor unit that does not support “I.U. ADD Initializa-
tion” function is not initialized even when “All” is specicated.
I.U. ADD Initialization
4 Select “Yes” and press “OK” to start the address initialization pro-
cess.
*If the address initialization is successfully completed, connection
check is automatically started.
02-04
Function Selection and Input/Output Initialization
This function re-establishes the function selection and Input/Output values to factory setting values.
1 Press and hold “
” (menu) and “ ” (return) simultaneously for at
least 3 seconds during the normal mode (when unit is not oper-
ated). The test run menu is displayed then.
2 Select “FUNC, Input/Output INITIAL” from the test run menu
pressing “
” and “OK”.
4 Individual remote controls
PC-ARF
TCGB0106 rev.0 - 12/2014
85
4

Table of Contents

Other manuals for Hitachi PSC-A1T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi PSC-A1T and is the answer not in the manual?

Hitachi PSC-A1T Specifications

General IconGeneral
BrandHitachi
ModelPSC-A1T
CategoryController
LanguageEnglish

Related product manuals