3 Select the indoor unit by pressing “ ” and press “OK”.
*This screen is not displayed when the number of indoor units con-
nected with the remote control switch is 1 (one). In this case, go
directly to the step 4..
FUNC, Input/Output INITIAL.
4 To start initialization, select “Yes” and press “OK” on the con-
rmation screen. It takes approx. 30 seconds to complete the
process.
*Check that initialization does not cause any problems, and then
start the initialization work.
02-04
5 Select “Completed” and press “OK”. The test run menu is dis-
played then.
Press “
” (return) on the test run menu to return to the normal mode.
To initialize setting for the other indoor units, select “I.U. Select” and
press “OK”. The screen returns to step 3.
FUNC, Input/Output INITIAL.: 02-04
NOTE
• “No Function” is indicated when the indoor unit that does not support the initialization function for “Function Selection” and “Input/
Output Setting”.
• The setting for indoor units that does not support the initialization function for “Function Selection” and “Input/Output Setting” is not
initialized even when “All” is specied at step 3.
Compressor Preheating Cancellation
This function cancels the compressor preheating control.
1 Press and hold “
” (menu) and “ ” (return) simultaneously for at
least 3 seconds during the normal mode (when unit is not oper-
ated). The test run menu is displayed then.
COMP Preheating CANC
Contact Information
2 Select “COMP Preheating CANC” from the test run menu press-
ing “
” and “OK”, then the conrmation screen is displayed.
3 Select “Yes” and press “OK”. The test run menu is displayed after
the setting is conrmed. If “No” is pressed, the screen returns to
test run menu.
COMP. Preheating Control CANC
Cancel preheating control
for compressor?
4 Press “ ” (return) on the test run menu to return to the normal mode.
4 Individual remote controls
PC-ARF
TCGB0106 rev.0 - 12/2014
86