EasyManuals Logo

Hitachi PSC-A1T Technical Catalogue

Hitachi PSC-A1T
774 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #148 background imageLoading...
Page #148 background image
4 Individual remote controls
PC-ART
TCGB0106 rev.0 - 12/2014
132
Items
Optional Func-
tion
Indi-
vidual
Setting
Setting
Condi-
tion
Contents
CF
Change of
Louver Swing
Angle
00
Standard (7
Steps)
01
Draft Prevention
(5 Steps)
02
High Ceiling (5
Steps) (*2)
d1
Power Supply
ON/OFF 1
00 Not Available
01 Available
d2
Not Prepared -
“- -”
Fixed
Not Used
d3
Power Supply
ON/OFF 2
00 Not Available
01 Available
d4
Prevention
for Cooling
Discharge Air
Temp. De-
crease
00 Not Available
01 Available
d5
Prevention
for Heating
Discharge Air
Temp. De-
crease
00 Not Available
01 Available
d6
Room Temp.
Control for En-
ergy Saving
00 Not Available
01 Available
d7
Not Prepared 00~07
Not Used
(Use as 00 condi-
tions)
E1
KPI: Ventila-
tion mode
00
Automatic Venti-
lation
01
Ventilation with
Total Heat Ex-
changer
02
Ventilation with
Bypass
(No Total Heat
Exchange)
Econofresh: all
fresh mode
00 Not Available
01/02 All fresh mode
E2
KPI: Increas-
ing Air Supply
Volume
00 Not Available
01 Available
Econofresh:
Enthalpy Sen-
sor
00 Not Available
01 Available
E3
Not Prepared
00 Not Used
01
(Use as 00 condi-
tions)
E4
KPI: Pre-
cooling / Pre-
Heating period
00 Standard
01 30 minutes
02 60 minutes
Econofresh:
gas sensor
00 Standard
01/02 CO
2
Sensor
E5
Not Prepared
00 Not Used
01
(Use as 00 condi-
tions)
Items
Optional Func-
tion
Indi-
vidual
Setting
Setting
Condi-
tion
Contents
E6
Indoor Fan
Operation
Time After
Cooling Op-
eration Stop-
page
00 Not Available
01 60 min.
02 120 min.
E7
Not Prepared -
00 Not Used
01
(Use as 00 condi-
tions)
E8
Fan Opera-
tion Control at
Heating Ther-
mo-OFF
00 Not Available
01 Available
E9
Not Prepared -
00 Not Used
01
(Use as 00 condi-
tions)
EA
Not Prepared
00 Not Used
01
(Use as 00 condi-
tions)
Eb
Fan Opera-
tion Control at
Cooling Ther-
mo-OFF
00 Not Available
01 LOW
02 SLOW
EC
Forced
Thermo-ON
Stoppage at
Cooling
00 Not Available
01 Available
Ed
Not Prepared
00 Not Used
01
(Use as 00 condi-
tions)
EE
Automatic Fan
Speed Control
00 Not Available
01 Available
F1
Automatic
Timer OFF
Setting
×
00 Function not valid
01 1 h
02 2 h
03 3 h
04-24 (04-24) h
0A 0.5 h
0B 1.5 h
F2
Main and sec-
ondary remote
control Setting
×
00 Master
01 Slave
F3
Automatic
Temperature
Setting Re-
lease
×
00 Not available
01 Available
F4
Automatic
Release Time
×
00
30 minutes (Fac-
tory setting)
01 15 minutes
02 60 minutes
03 90 minutes

Table of Contents

Other manuals for Hitachi PSC-A1T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi PSC-A1T and is the answer not in the manual?

Hitachi PSC-A1T Specifications

General IconGeneral
BrandHitachi
ModelPSC-A1T
CategoryController
LanguageEnglish

Related product manuals