4 Individual remote controls
PC-ART
TCGB0106 rev.0 - 12/2014
134
Table B Input and Output number display and connectors
Input number display
Port
Factory Setting
Setting
Input / Output Indication Setting Item Indiicaton
Input1

CN3 1-2 Remote ON/OFF 1 (level) 03
Input2
2
CN3 2-3
Forbidding Remote Control
after Manual Stoppage
06
Output1
1
CN7 1-2 Operation 01
Output2
2
CN7 1-3 Alarm 02
Output3
3
CN8 1-2 Thermo-ON for Heating 06
Table C Input and Output settings and display codes
Indication Input Output
00 Not set Not set
01 Room Thermostat (for Cooling) Operation
02 Room Thermostat (for Heating) Alarm
03 Remote ON/OFF 1 (level) Cooling
04 Remote ON/OFF 2 (Operation) Thermo-ON for Cooling
05 Remote ON/OFF 2 (Stoppage) Heating
06 Forbidding Remote Control after Manual Stoppage Thermo-ON for Heating
07 Remote Cooling / Heating Change Total Heat Exchanger
NOTE
After at least 3 minutes from the power ON, change the optional setting.
Record the setting conditions for each input and output in the “Setting” column of the table.