4 Individual remote controls
PC-ART
TCGB0106 rev.0 - 12/2014
141
4
F2 Remote Control Master-Slave Setting
This function is used when two remote control switches are installed in one system.
Set one remote control switch to “Master” 00, another remote control switch to “Slave” 01.
F3 Automatic Reset of Setting Temperature
This function is used to economize the operation. When this function is valid, the setting temperature is automatically 
returned to the Automatic Reset Temperature for Cooling/Heating (55/56) as following condition. If no change for certain 
period of Automatic Reset Time (54) since setting temperature was changed.
It is effective to optimize the setting temperature and provide energy saving.
However, the setting temperature is not automatically restarted in case that “Automatic COOL/HEAT Operation” mode, or 
“Prohibiting Operation by Remote Control Switch” is set at the central control equipment.
Setting Temperature 
Change
Operation Mode
 COOL
 DRY
 FAN
Operation Mode
 HEAT
Setting Temperature 
Change
Return to (56) Automatic Reset 
Temperature for Heating
Return to (55) Automatic Reset 
Temperature for Cooling
Example: Automatic Reset Temperature for Cooling is 25 ºC
Setting temperature is 
changed from 25 to 20 ºC by 
the remote control switch
Cooling operation at 20 
ºC is performed tempo-
rarily
If no operation for a de-
ned period, the setting 
temperature returns to 25 
ºC automaticaly
F4 Automatic Reset Time
This function is used to set the automatic reset time with the setting temperature. The setting conditions and automatic 
reset time are as follows:
Setting Condition Automatic Reset Time of Setting Temperature
00 30 minutes (Factory-Setting)
01 15 minutes
02 60 minutes
03 90 minutes