Initial Power on Setting
Turn on the power supply of the air conditioners.
To protect the compressor, the power supply should be
turned on 12 hours before starting operation. Do not turn
the power supply off during air conditioning seasons.
Perform a test run of each air conditioner rst to ensure
normal operation.
Turn on the power supply of the central station.
“Start-up” is displayed for a while during the boot pro-
cess, after which the screen changes to “Monitor 1 (All
Groups)”.
Start-up
Restore Setting
Press and hold “Restore” button for at least 5 seconds.
Restore
Language Setting
When turning the power supply ON for the rst time, the
language setting screen is displayed after a few minutes.
Select the using language for operation and tap “OK”.
Select the language and tap “OK”.
Español
Deutsch
Italiano
OK
English
Français
Adjusting Date/Time
After setting the language, the screen for adjusting date
and time screen is displayed on the touchscreen as shown
in the gure.
Tap “Set” on the touchscreen display, and set the date and
time following the indicated procedure.
Refer to the Adjusting Date/Time section in the Menu
chapter for detailed information.
NOTE
Setting the date and time may be required after a prolonged power
failure. If “Set Date/Time” is displayed on the screen in such a
case, then tap “Set” to adjust the date and time.
Set Date/Time
Set
Group Register
Register the connected indoor units to the groups and
blocks of the central station.
Tap “Set” on the touchscreen and the setting screen is
displayed. (When the power supply is turned ON at the
rst time.)
The registrable number of letters is maximum 20 for the
name of the group (block).
Register Group
Set