Exception Setting of Run/Stop Operation
This function is used in cases of exception to the command of “All Groups Run/Stop” operation and “Run/Stop by Block”
operation to the selected groups or blocks.
Selecting of “Exception Setting of Run/Stop Operation” (All Groups/Block) is available as follows.
Run and Stop
Run
Stop
NOTE
“All Run/Stop” and “Run/Stop by Block” command will not be affected when they are set to the groups/blocks. However, these com-
mands are affected as follows even this function is set.
- Scheduled Timer Operation.
- “All Run/Stop” and “Run/Stop by Block” by External Input command.
“Run/Stop” operation is available when the group is selected individually.
Selecting of exception operation
1 Select “Exception Setting of Run/Stop Operation” on the screen of “Service Menu”.
2 Select “Selecting of Exception Ope.” on the screen of “Exception of Run/Stop Ope.”
Back
Service Menu
25/01/2010 (Mon) 10:20
Group Register
Optional Function
Setting
Exception Setting
of Run/Stop
Operation
External
Input/Output Setting
Exception
External Input
Demand Function
Setting
Button Setting
Alarm History
Checking
Connection
Restore Setting
Contact Info.
Register
(1)
Back
Exception of
Run/Stop Ope.
25/01/2010 (Mon) 10:20
Selecting of
Exception Ope.
Selecting of
Exception Groups
(2)
3 Select the operation button for exception.
The selected button is rimmed with orange line.
4 Tap “Done” to return to the screen of “Exception of Run/Stop Ope.”
NOTE
If the target groups for the exception setting of Run/Stop operation are not selected, tap “Selecting of Exception Groups” and select the
target groups.
5 Tap “Back” to return to the screen of “Service Menu”.
Done
Exception of
Run/Stop Ope.
25/01/2010 (Mon) 10:20
Run and Stop Run Stop
(3)
(4)
Back
Exception of
Run/Stop Ope.
25/01/2010 (Mon) 10:20
Selecting of
Exception Ope.
Selecting of
Exception Groups
(5)
5 Centralised remote controls
PSC-A64GT
TCGB0106 rev.0 - 12/2014
275
5