6 Building air conditioning controls
CSNET WEB (PSC-A160WEB1)
TCGB0106 rev.0 - 12/2014
479479
6
Select a power meter device on the table and congure its data.
• Power Meter ID: identies the power meter.
• IP: Net address to communicate with the power meter device.
• Registers: The Modbus Address and the measurement unit of each of the four variables available on the table should
be congured by the user according to the specic power meter information.
Units screen is used to set the power meter devices to each of the available outdoors.
Select the Power meter ID on the combo box, select the units on the table and press button “Set”. The device will be linked
to the outdoor unit.