7 Gateways for building management systems
KNX001
TCGB0106 rev.0 - 12/2014
661661
7
3 Indicates the time in seconds that these requests will be delayed to prevent overload in the KNX bus,
due to other KNX devices behaving in the same way.
6
5
7
1
2
3
8
4
CSNET WEB settings
1 CSNET WEB IP address.
2 CSNET WEB TCP port, normally 502.
3 Timeout between data requests to CSNET WEB.
4 List of devices to use. For a device to be used in the KNX, it must be selected in the check box in the list. Each device
has the following properties:
5 System No., identies each Hitachi refrigeration system.
6 Unit No., identies each Hitachi unit.
7 Descriptive name of the device. An optional eld.
8 Permits selection of the number of devices to be used in the installation. On changing this parameter the conguration
window closes. When it is opened again, the number of devices selected will appear in the list. Up to 128 devices are
allowed.