Para.
No.
Address
Name
Value Range
Default
Unit
Change
Page
F0-05 61445
Base value of range of
auxiliary frequency
source Y for
superposition
0: Relative to maximum frequency
1: Relative to main frequency X
0 - At once
“
F0-05
”
on page
213
F0-06 61446
Range of auxiliary
frequency source Y for
superposition
0% to 150% 100 % At once
“
F0-06
”
on page
213
F0-07 61447
Frequency source
superposition
Ones:
0: Main frequency reference X
1: Main and auxiliary operation result
(based on tens)
2: Switchover between main frequency
X and auxiliary frequency Y
3: Switchover between main frequency
X and the main and auxiliary operation
result
4: Switchover between auxiliary
frequency Y and the main and auxiliary
operation result
Tens:
0: Main + Auxiliary
1: Main – Auxiliary
2: Max. (main, auxiliary)
3: Min. (main, auxiliary)
4: Main x Auxiliary
0 - At once
“
F0-07
”
on page
213
F0-08 61448
Preset frequency
0.00 Hz to 655.35 Hz 50.00 Hz At once
“
F0-08
”
on page
215
F0-09 61449
Running direction
0: Same as default direction
1: Reverse to default direction
0 - At once
“
F0-09
”
on page
215
F0-10 61450
Maximum frequency
50.00 Hz to 600.00 Hz 50.00 Hz
At stop
“
F0-10
”
on page
215
F0-11 61451
Source of frequency
upper limit
0: Frequency upper limit reference (F0-
12)
1: AI1
2: AI2
3: AI3
4: Reserved
5: Communication
6: Multi-speed reference
0 -
At stop
“
F0-11
”
on page
215
F0-12 61452
Frequency upper limit
0.00 Hz to 655.35 Hz 50.00 Hz At once
“
F0-12
”
on page
216
List of Drive Unit Parameters
-140-