Para.
No.
Address
Name
Value Range
Default
Unit
Change
Page
F9-01 63745
Motor overload
protection gain
0.20 to 10.00 1.00 - At once
F9-01
on page
294
F9-02 63746
Motor overload pre-
warning coefficient
50% to 100% 80 % At once
F9-02
on page
294
F9-06 63750
Output phase loss
detection before startup
0: Disabled
1: Enabled
0 % At once
F9-06
on page
295
F9-07 63751
Detection of short-circuit
to ground
0: Not detection
1: Detection before power-on
1 -
At stop
F9-07
on page
295
F9-09 63753
Auto reset attempts
0 to 20 0 - At once
F9-09
on page
295
F9-10 63754
DO action during auto
fault reset
0: Not act
1: Act
0 - At once
F9-10
on page
295
F9-11 63755
Auto reset interval
0.1s to 100.0s 1.0 s At once
F9-11
on page
295
F9-12 63755
Restart interval upon
fault reset
0s to 100.0s 1.0 s At once
F9-12
on page
296
F9-13 63757
STO safety state reset
mode
0: Manual
1: Auto
0 -
At stop
F9-13
on page
296
F9-14 63758
1st fault type
0 to 99
Model
dependent
-
Unchangeable
F9-14
on page
296
F9-15 63759
2nd fault type
0 to 99
Model
dependent
-
Unchangeable
F9-15
on page
296
F9-16 63760
3rd (latest) fault type
0 to 99
Model
dependent
-
Unchangeable
F9-16
on page
297
F9-17 63761
Frequency upon the 3rd
(latest) fault
-
Model
dependent
-
Unchangeable
F9-17
on page
297
F9-18 63762
Current upon the 3rd
(latest) fault
-
Model
dependent
-
Unchangeable
F9-18
on page
297
F9-19 63763
Bus voltage upon the 3rd
(latest) fault
-
Model
dependent
-
Unchangeable
F9-19
on page
297