EX4300 Site Guidelines and Requirements
IN THIS SECTION
Environmental Requirements and Specicaons for EX Series Switches | 124
General Site Guidelines | 131
Site Electrical Wiring Guidelines | 131
Rack Requirements | 132
Cabinet Requirements | 134
Clearance Requirements for Airow and Hardware Maintenance for EX4300 Switches | 135
Environmental Requirements and Specicaons for EX Series Switches
The switch must be installed in a rack or cabinet housed in a dry, clean, well-venlated, and
temperature-controlled environment.
Ensure that these environmental guidelines are followed:
The site must be as dust-free as possible, because dust can clog air intake vents and lters, reducing
the eciency of the switch cooling system.
Maintain ambient airow for normal switch operaon. If the airow is blocked or restricted, or if the
intake air is too warm, the switch might overheat, leading to the switch temperature monitor shung
down the switch to protect the hardware components.
Table 54 on page 125 provides the required environmental condions for normal switch operaon.