NOTE: Install the device only in restricted areas, such as dedicated equipment
rooms and equipment closets, in accordance with Articles 110–16, 110–17,
and 110–18 of the National Electrical Code, ANSI/NFPA 70.
Related
Documentation
Clearance Requirements for Airflow in and Hardware Maintenance of the Junos Pulse
Gateway on page 33
•
Junos Pulse Gateway Electrical and Power Requirements
There are factors you must consider while planning the electrical wiring and power
availability at your site. These factors include the following:
•
Power specifications and requirements for the device
•
Electrical wiring guidelines for the device installation site
•
Power, connection, and power cord specifications for the device
•
Grounding guidelines and specifications for the device
The power requirements vary greatly depending upon your configuration. Use the following
AC power specifications as a general rule.
Table 19: Power Specifications for an AC Power Supply Used in the MAG
Series Junos Pulse Gateway
MAG6611MAG6610MAG4611MAG4610MAG2600Item
Operating
range—100
through 240
VAC
Operating
range—100
through 240
VAC
Operating
range—100
through 240
VAC
Operating
range—100
through 240
VAC
Operating
range—100
through 240
VAC
AC input
voltage
50 through 60
Hz
50 through 60
Hz
50 through
60 Hz
50 through
60 Hz
50 through 60
Hz
AC input line
frequency
10 A8 A1 A1 A1 AAC input
current rating
750-W560-W70-W70-W30-WAC output
power
Modular
(removable)
Modular
(removable)
FixedFixedExternal brick
power supply
Type
Related
Documentation
• AC Power Cord Specifications for the MAG6610 and MAG6611 Junos Pulse Gateway
on page 35
29Copyright © 2014, Juniper Networks, Inc.
Chapter 4: Site Preparation