Table 21: Cabinet Requirements and Specifications
Guidelines
Cabinet
Requirement
You can mount the Junos Pulse Gateway in a cabinet that contains a 19-in.
rack as defined in Cabinets, Racks, Panels, and Associated Equipment
(document number EIA-310–D) published by the Electronics Industry
Association (http://www.eia.org).
NOTE: The rack must meet the strength requirements to support the weight
of the Junos Pulse Gateway.
The minimum cabinet size must be accommodate the maximum external
dimensions of the Junos Pulse Gateway.
Cabinet size
The outer edges of the mounting brackets extend the width of the chassis to
19-in. (48.3-cm).
The minimum total clearance inside the cabinet is 30-in. (76.2-cm) between
the inside of the front door and the inside of the rear door.
Cabinet
clearance
When you mount the Junos Pulse Gateway in a cabinet, ensure that ventilation
through the cabinet is sufficient to prevent overheating.
Ensure adequate cool air supply to dissipate the thermal output of the Junos
Pulse Gateway.
Ensure that the cabinet allows the chassis hot exhaust air to exit the cabinet
without recirculating into the Junos Pulse Gateway. An open cabinet (without
a top or doors) that employs hot air exhaust extraction from the top allows
the best airflow through the chassis. If the cabinet has a top or doors,
perforations in them can help remove the hot air exhaust.
Install the Junos Pulse Gateway in the cabinet in a way that maximizes the
open space on the side of the chassis with the hot air exhaust. This maximizes
the clearance for critical airflow.
Route and dress all cables to minimize the blockage of airflow to and from
the chassis.
Ensure that the spacing of rails and adjacent cabinets allows for proper
clearance around the Junos Pulse Gateway and cabinet.
A cabinet larger than the minimum required provides better airflow and
reduces the chance of overheating.
Cabinet
airflow
Related
Documentation
Clearance Requirements for Airflow in and Hardware Maintenance of the Junos Pulse
Gateway on page 33
Clearance Requirements for Airflow in and Hardware Maintenance of the Junos Pulse
Gateway
When planning the installation site for the Junos Pulse Gateway, you need to allow
sufficient clearance around the rack or cabinet where you are planning to install the
device.
33Copyright © 2014, Juniper Networks, Inc.
Chapter 5: Rack and Cabinet Requirements

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper Junos Pulse MAG2600 and is the answer not in the manual?

Juniper Junos Pulse MAG2600 Specifications

General IconGeneral
BrandJuniper
ModelJunos Pulse MAG2600
CategoryGateway
LanguageEnglish

Related product manuals