Table 61: Routers Environmental Specifications
ValueDescription
No performance degradation to 10,000 ft (3048 m)Altitude
Normal operation ensured in relative humidity range of 5% to 90%,
noncondensing
Relative humidity
Normal operation ensured in temperature range of 32°F (0°C) to
104°F (40°C)
Nonoperating storage temperature in shipping container:
–40°F (–40°C) to 158°F (70°C)
Temperature
Designed to meet Telcordia Technologies Zone 4 earthquake
requirements
Seismic
AC power: 7161 BTU/hour (2100 W)
DC power: 5074 BTU/hour (1488 W)
Maximum thermal output
NOTE: Install the routeronlyin restricted areas, such as dedicated equipment
rooms and equipment closets, in accordance with Articles 110-16, 110-17, and
110-18 of the National Electrical Code, ANSI/NFPA 70.
Related
Documentation
Routine Maintenance Procedures for the MX240 Router on page 375
General Safety Guidelines for Juniper Networks Devices
General Safety Warnings for Juniper Networks Devices
Compliance Statements for Environmental Requirements for Juniper Networks Devices
on page 481
MX240 Site Preparation Checklist
The checklist in Table 62 on page 111 summarizes the tasks you must perform when
preparing a site for router installation.
Table 62: Site Preparation Checklist
DatePerformed ByFor More InformationItem or Task
“MX240 Router Environmental
Specifications” on page 110
Verify that environmental factors such as
temperature and humidity do notexceed router
tolerances.