6. Arrange the cable to prevent it from dislodging or developing stress points. Secure
the cable so that it is not supporting its own weight as it hangs to the floor. Place
excess cable out of the way in a neatly coiled loop.
CAUTION: Avoid bending fiber-optic cable beyond its minimum bend
radius.An arcsmaller than a few inches in diameter can damage the cable
and cause problems that are difficult to diagnose.
7. For an FPC3 PIC, loosen the captive screw at the bottom of the PIC faceplate, then
twist the ejector handle at the top of the faceplate counterclockwise to unseat the
PIC.
8. Slide the PIC out of the FPC card carrier and place it in the electrostatic bag or on the
antistatic mat.
9. If you are not reinstalling a PIC into the emptied PIC slot within a short time, install a
blank PIC panel over the slot to maintain proper airflow in the FPC card cage.
Figure 142: Removing a PIC
g004412
317Copyright © 2017, Juniper Networks, Inc.