Protection functions
© 2022 KEB Automation KG
107
pn87[6]
blockage detection status
0x2A57 [6]
Value
Plaintext
Note
3
blockage reaction hold
The timer pn87[3] detection time has expired and the
torque / current is held
4
blockage reaction time
running
The blockage reaction is running and the torque/current is
decayed.
5
blockage reaction fin-
ished
A blockage is detected, the reaction is finished
This state is always left by switching off the modulation
and, depending on the setting in pn78[1], also at setpoint
speed equal to zero or change of the setpoint direction of
rotation.
The current and the torque are no longer affected by the
blockage.
The internal setpoint is held at zero.