Status displays
© 2022 KEB Automation KG
205
5.8.2.6 Others (3 Bit)
ru76
drive state
Bit 18…20
others
Bit
Valu
e
Mult.
Plaintext
Notes
18…20
0
262144
No special function active
1
ssf
Speed search function active
2
ident
Motor identification active
3
flux
Flux formation active (ASM)
4
brake
one of the brake downtimes is running
6
fault reaction
Fault reaction ramp is active
5, 7
reserved
5.8.2.7 Example
If the drive is in the following state:
ru76
drive state
State
Bit group
Valu
e
Mult.
Meaning
modulation state
0…4
1
1
Modulation active
modes of Operation
5…8
2
32
Velocity mode is active
actual motor
9…11
1
512
Motor type is synchronous motor
actual control
12…14
2
4096
Operation with encoder and motor model
ramp state
15…17
3
32768
actual ramp state = forward constant run
others
18…20
0
262144
No special function active
the following parameter value results for ru76
1 * 1 + 2 * 32 + 1 * 512 + 2 * 4096 + 3 * 32768 + 0 * 262144 = 107073dec. =
0001A241hex.
Display:
MON + VL + SM + Enc+Model + forward const
de115 global drive state mask
Index
Id-Text
Name
Function
0x2073
de115
global drive state mask
Masking of single bits of ru75
Single bits of ru75 and ru76 can be switched off with this object.
Example: de115 = 0x0F0000. Only the ramp state is visible in ru75 with this set-
ting. All other bits are suppressed.