Errors and warnings
46
© 2022 KEB Automation KG
21
1fghfh
1
Figure 3: Process of a fault reaction
4.3.1.2.4 Fault reaction properties
The behavior of the fault reaction can be influenced via object pn62.
Index
Id-Text
Name
Function
0x2A1E
pn62
Fault reaction properties
Properties of the fault reaction
The meaning of the single bits in pn62 is defined as follows:
pn62
fault reaction properties
0x2A3E
Bit
Name
Note
0
Speed src
Source for the starting speed of the deceleration ramp
0: Setpoint speed (output ramp generator)
1: Actual speed
4.3.1.2.5 Error reaction/stop_function torque limit
Another (higher) torque limit is required in some applications for the state Fault re-
action active.
It is often requested to decelerate with maximum torque (e.g. at the limiting charac-
teristic), then to reduce the torque to a small residual value during the standstill
phase (e.g. in order to relieve a shaft) before the modulation is then switched off.
Which torque limit shall be active during fault reaction can be selected in co61 Bit
0...5.