Analog inputs
© 2022 KEB Automation KG
469
an30
ref and aux function
0x331E
Bit
Function
Value
Plaintext
Notes
0…3
ref input
0
off
REF = 0
1
AN1
REF = AN1
2
AN2
REF = AN2
3
PID
REF = PID Output
4…7
A input
0
off
A input = 0
16
AN1
A input = AN1
32
AN2
A input = AN2
48
PID
A input = PID Output
64
ANOUT1
A input = ru78 Analog Output
80
ANOUT2
A input = an44 ANOUT2 display
96
ANOUT3
A input = an47 ANOUT3 display
8…11
B input
0
off
B input = 0
256
AN1
B input = AN1
512
AN2
B input = AN2
768
PID
B input = PID Output
1024
ANOUT1
A input = ru78 Analog Output
1280
ANOUT2
A input = an44 ANOUT2 display
1536
ANOUT3
A input = an47 ANOUT3 display
12…15
aux function
0
off
AUX = 0
4096
A
AUX = A
8192
A + B
AUX = A + B
12288
A * (1+B)
AUX = A * (1+B)
16384
A * B
AUX = A * B
20480
|A|
AUX = |A| (absolute value of A)
Mapping of REF and AUX
AUX (ru49) and REF (ru48) are limited to +/- 400% after the calculation. Then these two
values can be set to any objects with the following settings.
Index
Id-Text
Name
Function
0x331F
an31
REF selector
Determination which object is affected by REF
0x3320
an32
REF norm fact
Scaling of the analog setpoint to the selected object.
0x3321
an33
REF norm status
Status of the standardization function
0x3322
an34
AUX selector
Determination to which object AUX acts on
0x3323
an35
AUX norm fact
Scaling of the analog setpoint to the selected object.
0x3324
an36
AUX norm status
Status of the standardization function
The address of any object which is to be influenced by the analog values can be adjusted
directly in an31 and an34.
All writable objects that are also permissible for process data are permitted.
If, for example, the setpoint speed shall be preset analog via vl20 target velocity (address
0x2314), an31 = 0x2314 must be adjusted.
The analog setpoint is standardized and by way adapted to the required value range of
the objects with an32 REF norm fact and an35 AUX norm fact.
The values are written with the same standardization functions, over which the objects
are accessible also via bus system.