EasyManua.ls Logo

KEB COMBIVERT F6

KEB COMBIVERT F6
544 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Braking transistor
122
© 2022 KEB Automation KG
WARNING
Exception: the braking resistor is activated again, regardless of its tempera-
ture, when the DC link voltage exceeds the OP2 threshold ("extreme overpo-
tential").
NOTICE
Since the drive does not contain a real-time clock, the time when the control
board has been switched off is unknown. Thus, the cooling time for the sub-
mounted braking resistor is also unknown.
The calculated temperature of the braking resistor is stored every 5 seconds. Af-
ter switching on again, the display of the resistance starts with the last stored
value.

Table of Contents

Other manuals for KEB COMBIVERT F6

Related product manuals