No special function active
Speed search function active
Motor identification active
Flux formation active (ASM)
one of the brake downtimes is running
Fault reaction ramp is active
5.8.2.7 Example
If the drive is in the following state:
Motor type is synchronous motor
Operation with encoder and motor model
actual ramp state = forward constant run
No special function active
the following parameter value results for ru76
1 * 1 + 2 * 32 + 1 * 512 + 2 * 4096 + 3 * 32768 + 0 * 262144 = 107073dec. =
0001A241hex.
Display:
MON + VL + SM + Enc+Model + forward const
de115 global drive state mask
Masking of single bits of ru75
Single bits of ru75 and ru76 can be switched off with this object.
Example: de115 = 0x0F0000. Only the ramp state is visible in ru75 with this set-
ting. All other bits are suppressed.