Motor parameterization
© 2022 KEB Automation KG
387
Index
Id-Text
Name
Function
0x243C
ds60
protection function
Parameter structure for the definition of overcurrent / overvoltage
behaviour
Subidx
Name
Function
1
v/f current limit control mode
Current controller access in v/f operating mode
2
ramp stopping mode
Mode for LAD-Stop (I/U)
3
LD-U stop voltage level
DC link voltage setpoint for the LD (U) stop function
4
LAD-I KI [1/As]
Integral gain factor (KI) for current-dependent change of acceler-
ation / deceleration ramps
5
LAD-I KDI [1/As]
Differential + integral gain factor (KD + KI)
Evaluation of the current rise with integration.
The ACC/DEC ramp is also reduced below the current level
Imax
(*1)
depending on the rate of current rise
6
LD-U KI [1/Vs]
Integral gain factor (KI) for DC voltage-dependent change of the
deceleration ramps
7
LD-U KDI [1/Vs]
Differential + integral gain factor (KD + KI)
Evaluation of the voltage rise with integration.
The DEC ramp is also reduced below ds60[3] LD-U stop voltage
level depending on the rate of voltage rise.
(*1)
The maximum current "Imax" is formed from the following parameters: dr12
max. current %, is11 max current [de28%], is35 set current limit, is14 overload pro-
tect mode
ds60
v/f current limit control
0x243C SubIdx 1
Bit
Function
Valu
e
Plai
ntext
Function
0
always activ
0
off
No current controller active
1
on
Current controller becomes active if the activation
condition is fulfilled
1
active at n <
10%Nn
0
off
Activation if the speed is less than 10% of the rated
speed (dr04 rated speed)
2
on
The maximum current is formed from the following parameters: dr12 max. current %, is11 max
current [de28%], is35 set current limit, is14 overload protect mode and (only when DC braking
is active) ds62[4] max.DC current