Digital Inputs
430
© 2022 KEB Automation KG
Now the DC braking can be activated by setting bit 12 in the controlword (0x2500
or 0x6040).
CAUTION
If bus communication is interrupted, the last status of the control-
word inputs is retained. This can cause an unwanted permanent func-
tion activation
The option deactivate braking transitor in error case in connection
with suitable parameterization of the watchdog error can provide a
remedy.