The PID controller is completely deactivated
Analog input 1 is actual value source
Analog input 2 is actual value source
PID actual value is preset via an67 in the range -400.0% ... 400.0%
Active current ru11 act active current / rated motor current dr03 corre-
sponds to 100.0%
Apparent current ru10 act. apparent current / rated motor current dr03 cor-
responds to 100.0%
DC link voltage ru14 act Uic voltage / 1000V corresponds to 100%
Active power ru82[2] electrical output power
Rated device power Un * In * corresponds to 100%
Actual torque ru24 actual torque / rated motor torque dr09 corresponds to
100%
Inverter utilization = apparent current / rated device current de28
The value of ru78 Analog Out display is the actual value source.
4096 → 100%
an44 ANOUT2 display is the actual value source.
4096 → 100%
an47 ANOUT3 display is the actual value source.
4096 → 100%