Address Name / seng range / [default seng] Informaon
0x29E1 Field weakening controller Field limitaon
5.00 ... [100.00] ... 100.00
%
From version 04.00
Field limitaon of the eld weakening controller.
9.4.6.5 ASM
eld weakening controller (extended)
For a quick commissioning, the calculaons and sengs are made automacally during the
motor calibraon.
Precondions
The eld weakening controller is only eecve in the motor control type "Sensorless vector
control (SLVC)".
Parameter
Address Name / seng range / [default seng] Informaon
0x29E2 DC-bus lter me
1.0 ... [25.0] ... 1000.0
ms
Filter me for the current DC-bus voltage used for eld weakening.
0x29E3 Motor voltage lter me
1.0 ... [25.0] ... 1000.0 ms
Filter me for the current motor voltage used for eld weakening.
0x29E4
(P354.00)
Voltage reserve range
(Voltage reserve)
0 ... [5] ... 20 %
Voltage reserve at the transion point to the eld weakening, with
reference to the current value of the DC-bus voltage.
Is
eecve in sensorless vector control (SLVC) 40x2C00 (P300.00) = 4).
100 %
≡ DC-bus voltage 40x2D87 (P105.00)
Conguring the motor control
Opons for opmizing the control loops
Mot
or control sengs
186