Address Name / seng range / [default seng] Informaon
0x29E1 Field weakening controller Field limitaon
5.00 ... [100.00] ... 100.00
%
•
From version 04.00
Field limitaon of the eld weakening controller.
9.4.6.5 ASM
eld weakening controller (extended)
For a quick commissioning, the calculaons and sengs are made automacally during the
motor calibraon.
Precondions
The eld weakening controller is only eecve in the motor control type "Sensorless vector
control (SLVC)".
Parameter
Address Name / seng range / [default seng] Informaon
0x29E2 DC-bus lter me
1.0 ... [25.0] ... 1000.0
ms
Filter me for the current DC-bus voltage used for eld weakening.
0x29E3 Motor voltage lter me
1.0 ... [25.0] ... 1000.0 ms
Filter me for the current motor voltage used for eld weakening.
0x29E4
(P354.00)
Voltage reserve range
(Voltage reserve)
0 ... [5] ... 20 %
Voltage reserve at the transion point to the eld weakening, with
reference to the current value of the DC-bus voltage.
Is
eecve in sensorless vector control (SLVC) 40x2C00 (P300.00) = 4).
•
100 %
≡ DC-bus voltage 40x2D87 (P105.00)
Conguring the motor control
Opons for opmizing the control loops
Mot
or control sengs