7.2 Congure setpoint sources
The following setpoint sources are described in this chapter:
•
K
eypad ^ 68
•
Setpoint presets ^ 69
•
Motor potenometer (MOP) ^ 71
•
Sequencer ^ 73
Setpoint sources described in other chapters:
•
Analog input 1 ^ 205
•
Analog input 2 ^ 209
7.2.1 Keypad
For the manual setpoint selecon via keypad, the following default sengs are used:
Parameter
Address Name / seng range / [default seng] Informaon
0x2601:001
(P202.01)
Keypad setpoints: Frequency setpoint
(K
eypad setpoints: KP freq.setpoint)
0.0 ... [20.0] ... 599.0 Hz
Default seng of the keypad setpoint for the operang mode 0x6060
(P301.00) = "MS: Velocity mode [-2]".
0x2601:002
(P202.02)
Keypad setpoints: Process controller setpoint
(Keypad setpoints: KP PID setpoint)
-300.00 ... [0.00] ... 300.00 PID unit
Default seng of the keypad setpoint for the reference value of the PID
control.
The increment for keypad setpoints can be adapted in 0x2862 (P701.00) b
y pressing a keypad
arrow key once.
A switch-over to the keypad during operaon is also possible as an alternave to the standard
setpoint source seng.
4Ex
ample: Change-over from AI1 setpoint to keypad setpoint ^ 116
Related topics
4Keypad ^ 244
Conguring the frequency control
Congure setpoint sources