Address Name / seng range / [default seng] Informaon
0x261C:050
(P740.50)
Favorites
sengs: Parameter 50
(Favorites se.: Parameter 50)
0x00000000 ... [0x29110400] ... 0xFFFFFF00
4.5 Saving the parameter sengs
4.5.1 Save parameter sengs with keypad
If one parameter seng has been changed with the keypad but has not been saved in the
memor
y module with mains failure protecon, the SET display is blinking.
In order to save parameter sengs in the user memory of the memory module, press and
hold the enter key for longer than 3 s.
MAN MAN MANAUTO AUTO AUTOLOC LOC LOCREM REM REM
VEL
Saving Parameters Parameters S aved
:FLEX:AIN1
SET SET SET
> 3 s
0 0 0 S T O P S A V I N G P S P
S
A
V
E D
4.5.2 Save parameter sengs with »EASY Starter«
If a parameter seng has been changed with the »EASY Starter« but not yet saved in the
memory medium with mains failure protecon, the status line of the »EASY Starter« displays
the note "The parameter set was changed".
There are 3 opons to save the parameter sengs in the user memory of the storage medium
•
Click the buon in the toolbar of the »EASY Starter« .
•
Press the funcon key F6.
•
Execute the device command "Save user data": 0x2022:003 (P700.03) = "On / start [1]".
4.5.3 Automac storage in the memory module
Parameter
Address Name / seng range / [default seng] Informaon
0x2829
(P732.00)
Automac storage in the memory module
(Auto-Save EPM)
1 = Acvate automac saving of parameters in the memory module.
Saving is undertaken to a parameter stored on the memory module with
each write cycle. An excessively high number of write cycles reduces the
service life of the memory module.
•
With the seng 0, the "Save user data" 0x2022:003 (P700.03) device
command must be explicitly executed, or the enter key must be
pressed and held for longer than 3 s to save the current parameter
sengs in the memory module of the inverter with mains failure
protecon.
Warning
The "Automac saving" funcon must not be used together with cyclical
wring of parameters via PDO.
0 Inhibit
1 Enable
In contrast to the inverters of the i500 series, the i410 inverter is not provided
with a r
eplaceable memory module.
Commissioning
Sa
ving the parameter sengs
Automac storage in the memory module
29