4.5 Saving the parameter sengs
4.5.1 Save parameter sengs with keypad
If one parameter seng has been changed with the keypad but has not been saved in the
memor
y module with mains failure protecon, the SET display is blinking.
In order to save parameter sengs in the user memory of the memory module, press and
hold the enter key for longer than 3 s.
MAN MAN MANAUTO AUTO AUTOLOC LOC LOCREM REM REM
VEL
Saving Parameters Parameters S aved
:FLEX:AIN1
SET SET SET
> 3 s
0 0 0 S T O P S A V I N G P S P
S
A
V
E D
4.5.2 Save parameter sengs with »EASY Starter«
If a parameter seng has been changed with the »EASY Starter« but not yet saved in the
memory medium with mains failure protecon, the status line of the »EASY Starter« displays
the note "The parameter set was changed".
There are 3 opons to save the parameter sengs in the user memory of the storage medium
Click the buon in the toolbar of the »EASY Starter« .
Press the funcon key F6.
Execute the device command "Save user data": 0x2022:003 (P700.03) = "On / start [1]".
4.5.3 Automac storage in the memory module
Parameter
Address Name / seng range / [default seng] Informaon
0x2829
(P732.00)
Automac storage in the memory module
(Auto-Save EPM)
1 = Acvate automac saving of parameters in the memory module.
Saving is undertaken to a parameter stored on the memory module with
each write cycle. An excessively high number of write cycles reduces the
service life of the memory module.
With the seng 0, the "Save user data" 0x2022:003 (P700.03) device
command must be explicitly executed, or the enter key must be
pressed and held for longer than 3 s to save the current parameter
sengs in the memory module of the inverter with mains failure
protecon.
Warning
The "Automac saving" funcon must not be used together with cyclical
wring of parameters via PDO.
0 Inhibit
1 Enable
In contrast to the inverters of the i500 series, the i410 inverter is not provided
with a r
eplaceable memory module.
Commissioning
Sa
ving the parameter sengs
Automac storage in the memory module
29