9.3 Parameterisable motor funcons
9.3.1 Skip frequencies
By means of the three parameterisable skip frequencies, crical frequencies can be
suppr
essed which lead to mechanical resonances in the system.
Details
A blocking zone is acve as soon as the frequency for this blocking zone is set to a value ≠
"0 Hz".
•
The fr
equency
denes the center of the range to be masked out.
①
•
The bandwidth denes its total size.
②
Example: For a blocking zone, the frequency is set to 20 Hz and the bandwidth to 10 Hz.
These
sengs mask out the range from 15 Hz to 25 Hz.
Notes:
•
Skip frequencies are absolute values. With the seng "20 Hz", at the same me also the
skip frequency "-20 Hz" is dened.
•
The in
verter accelerates/decelerates the motor through the range to be masked out.
Connuous operaon within this range is not possible.
•
A blocking z
one is not acve if its bandwidth is set to "0 Hz".
Adjacent and overlapping areas:
•
Example on the le: If the ranges are closely spaced, the ranges are passed through as
shown.
•
Example on the right: If the ranges overlap, the lowest and highest value form a new
range. In the status display 0x291F:016, both ranges are shown as acve.
[Hz]
[Hz]
[Hz]
[Hz]
Output
Input Input
Output
Conguring the motor control
P
arameterisable motor funcons
Skip frequencies
156