12.3 Trigger acon if a frequency threshold is exceeded
As a funcon of the current output frequency, the adjustable frequency threshold serves to
trig
ger a certain funcon or set a digital output.
Parameter
Address Name / seng range / [default seng] Informaon
0x4005
(P412.00)
Frequency threshold
(Fr
eq. threshold)
0.0 ... [0.0] ... 599.0 Hz
Threshold for the "Frequency threshold exceeded [70]" trigger.
•
The "Frequency threshold exceeded [70]" trigger is TRUE if the
current output frequency is higher than the set threshold.
•
The trigger can be assigned to a funcon or to a digital output.
Example for operang mode
In the following example, the digital output 1 is set to TRUE if the output frequency is higher
than 20
Hz.
•
The analog input 1 is set as standard setpoint source.
•
Switch S1 starts the motor in forward direcon of rotaon. De-asserng Switch S1 stops
the motor again.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2634:002 (P420.02) Digital outputs funcon: Digital output 1 Frequency threshold exceeded [70]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2860:001 (P201.01) Frequency control: Default setpoint source Analog input 1 [2]
0x4005 (P412.00) Frequency threshold 20 Hz
Addional
funcons
Trigger acon if a frequency threshold is exceeded
242