9.2.7 Opmising the stalling behaviour
If the motor is driven with frequencies above the rated motor frequency, the operang point
is shied to the
"eld weakening range". In this range, the motor voltage does not increase
proporonately to the output frequency anymore. As a consequence, the inverter
automacally reduces the maximum current since the full torque is not available anymore at
these frequencies.
For special motors which enable an operaon in the eld weakening range, the behaviour in
the eld weakening range can be adapted to the motor with 0x2B0C (P319.00).
DANGER!
Danger by incorrect
parameterisaon.
Possible consequences: damage to material assets and injury to persons
Only change the default seng (0 Hz) in 0x2B0C (P319.00) aer consulng the motor
manufacturer!
Recommendaon: Maintain default seng (0 Hz).
Precondions
The
funcon is only eecve in the motor control type "V/f characterisc control (VFC open
loop)".
Conguring the motor control
V
/f characterisc control for asynchronous motor (VFC open loop)
Opmising the stalling behaviour