9.4.6.6 Imax controller
For a quick commissioning, the calculaons and sengs are made automacally during the
mot
or calibraon.
For typical applicaons, a manual adaptaon of the parameters of the Imax
c
ontroller is not recommended. A wrong seng may have a negave eect on
the control. For special applicaons, contact the manufacturer before adapng
the parameters.
Precondions
The Imax controller is only eecve in the motor control type "V/f characterisc control (VFC
open loop)".
Details
The Imax controller becomes acve in the V/f operaon if the actual motor current exceeds
the ma
ximum overload current "Max current". The Imax controller changes the output
frequency to counteract the exceedance.
The maximum overload current "Max current" is dened in 0x6073 (P324.00) in percent with
regard to the rated motor current "Motor rated current" 0x6075 (P323.00).
If the maximum overload current is exceeded:
•
During operaon in motor mode, the Imax controller reduces the output frequency.
•
During operaon in generator mode, the Imax controller increases the output frequency.
Seng notes
If oscillaons occur at the current limit during operaon:
•
R
educe gain of the Imax controller in 0x2B08:001 (P333.01).
•
Increase reset me of the Imax controller in 0x2B08:002
(P333.02).
•
Carry out the changes in small steps only (by 2 ... 3 % of the set value) unl the oscillaons
do not exist anymore.
If the Imax controller does not respond fast enough aer the maximum current has been
exceeded:
•
Increase gain of the Imax controller in 0x2B08:001 (P333.01).
•
Reduce reset me of the Imax controller in 0x2B08:002 (P333.02).
•
Carry out the changes in small steps only (by 2 ... 3 % of the set value in each case) unl
the response me is acceptable.
Parameter
Address Name / seng range / [default seng] Informaon
0x2822:019 Calculate Imax controller parameter
0 ... [0] ... 1
1 = start automac calculaon of the Imax controller parameters.
•
Gain 0x2B08:001
(P333.01) and reset me 0x2B08:002 (P333.02) of
the Imax controller are recalculated and set.
0x2B08:001
(P333.01)
V/f Imax controller: Gain
(V/f Imax contr.: Gain)
0.000 ... [0.284]* ... 1000.000 Hz/A
* Default seng dependent on the model.
Gain factor Vp of the Imax controller.
0x2B08:002
(P333.02)
V/f Imax controller: Reset me
(V/f Imax contr.: Reset me)
1.0 ... [2.3]* ... 2000.0 ms
* Default seng dependent on the model.
Reset me Ti of the Imax controller.
0x2DE0:010 V/f behavior
0 ... [0] ... 65535
•
Seng can only be changed if the inverter is
disabled.
•
From version 05.03
Calculaon source for slip in the V/f control.
Bit 0 Slip compensaon via equivalent circuit
diagram
Bit 0 = 0: calculaon via motor data label (standard).
Bit 0 = 1: calculaon of magnesing current based on equivalent circuit
diagram (response <= SW 05.02.00).
Conguring the motor control
Opons for opmizing the control loops
Mot
or control sengs