10 I/O extensions and control connecons
10.1 Congure digital inputs
Sengs for digital inputs 1 ... 5.
Details
The digital inputs are used for control tasks. For this purpose, the digital inputs are available as
select
able triggers for funcons.
The following sengs are possible for the digital inputs:
Debounce me
In
version
Trigger
1
0x2632:005
0x2633:001
0x2632:0020x2633:002
0x2632:0030x2633:003
DI1
1
0
0 t
DI2
0 t
DI3
0 t
1
0
1
1
0
1
DI4
0 t
1
0
1
0x2632:004
0x2632:001
0x2633:004
0x2633:005
0x60FD - Bit 16
0x60FD - Bit 17
0x60FD - Bit 18
0x60FD - Bit 19
0x60FD - Bit 20
DI5
0 t
1
0
1
X3
Digital input 5 [15]
Digital input 4 [14]
Digital input 3 [13]
Digital input 2 [12]
Digital input 1 [11]
Diagnosc parameters:
The logic s
tatus of the digital inputs is displayed in 0x60FD (P118.00).
Asseron level "HIGH acve"
HIGH
acve (default seng)
In
ternally, the digital input terminals are set to LOW level via pull-down resistors.
The current ows from the current supply (e.g. X3/24V) through the contact to the digital input terminal (and internally via the pull-down
r
esistor to GND).
If the contact is closed, the digital input is set to HIGH level and is thus HIGH acve.
Connecon plan (example):
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3
Debounce me
For minimising interference pulses, a debounce me of 1 ms is set for all digital inputs.
Via »E
ASY Starter« (or network), the debounce me for can be increased individually for each
digital input to maximally 50 ms.
I/O extensions and control connecons
203