12.2.1 Example:
Selecve control of several motors with one inverter
12.2.1.1
A typical applicaon for the parameter change-over is an applicaon/machine in which
several axes must be triggered successively but a simultaneous operaon of several motors is
not required. In this case, one and the same inverter can trigger the motors in succession.
Advantages of this soluon are the reduced amount of components (inverters) and a reduced
energy consumpon.
Principle:
•
The motor to be currently controlled is connected to the inverter via motor contactors.
(The contactor system can, for instance, be controlled via the digital outputs of the
inverter.)
•
At the same me, the motor and control sengs suitable for motor are acvated in the
inverter by means of parameter change-over.
M1
3~
M2
3~
M3
3~
M4
3~
Set 4
Set 3
Set 2
Set 1
Inverter
RAM
memory
□
Motor data change-over (via the "parameter change-over" funcon)
□
Motor change-over (e.g. via motor contactors)
The following table lists all parameters that require dierent sengs for the four motors:
# Parameter Name Seng
M1 M2 M3 M4
1 0x2B00 (P302.00) V/f characterisc shape Linear [0] Square-law [1] Linear [0] Linear [0]
2 0x2B01:002 (P303.02) Base frequency 60 Hz 60 Hz 60 Hz 50 Hz
3 0x2D4B:001 (P308.01) Maximum
ulisaon [60 s] 150 % 120 % 150 % 150 %
4 0x2B12:001 (P316.01) Fixed boost 2.5 % 0.0 % 4.0 % 2.0 %
5 0x2C01:004 (P320.04) Rated speed 1745 3450 1750 1450
6 0x2C01:005 (P320.05) Rated frequency 60.0 Hz 60.0 Hz 60.0 Hz 50.0 Hz
7 0x2C01:006 (P320.06) Rated power 0.75 kW 0.75 kW 0.75 kW 1.50 kW
8 0x2C01:007 (P320.07) Rated voltage 480 V 480 V 480 V 400 V
9 0x6075 (P323.00) Motor rated current 2,200 A 2,100 A 2,200 A 3,500 A
10 0x6073 (P324.00) Max current 200.0 % 150.0 % 200.0 % 200.0 %
Addional
funcons
Parameter change-over
Example: Selecve control of several motors with one inverter
232