12.2.1 Example:
Selecve control of several motors with one inverter
12.2.1.1
A typical applicaon for the parameter change-over is an applicaon/machine in which
several axes must be triggered successively but a simultaneous operaon of several motors is
not required. In this case, one and the same inverter can trigger the motors in succession.
Advantages of this soluon are the reduced amount of components (inverters) and a reduced
energy consumpon.
Principle:
The motor to be currently controlled is connected to the inverter via motor contactors.
(The contactor system can, for instance, be controlled via the digital outputs of the
inverter.)
At the same me, the motor and control sengs suitable for motor are acvated in the
inverter by means of parameter change-over.
M1
3~
M2
3~
M3
3~
M4
3~
Set 4
Set 3
Set 2
Set 1
Inverter
RAM
memory
Motor data change-over (via the "parameter change-over" funcon)
Motor change-over (e.g. via motor contactors)
The following table lists all parameters that require dierent sengs for the four motors:
# Parameter Name Seng
M1 M2 M3 M4
1 0x2B00 (P302.00) V/f characterisc shape Linear [0] Square-law [1] Linear [0] Linear [0]
2 0x2B01:002 (P303.02) Base frequency 60 Hz 60 Hz 60 Hz 50 Hz
3 0x2D4B:001 (P308.01) Maximum
ulisaon [60 s] 150 % 120 % 150 % 150 %
4 0x2B12:001 (P316.01) Fixed boost 2.5 % 0.0 % 4.0 % 2.0 %
5 0x2C01:004 (P320.04) Rated speed 1745 3450 1750 1450
6 0x2C01:005 (P320.05) Rated frequency 60.0 Hz 60.0 Hz 60.0 Hz 50.0 Hz
7 0x2C01:006 (P320.06) Rated power 0.75 kW 0.75 kW 0.75 kW 1.50 kW
8 0x2C01:007 (P320.07) Rated voltage 480 V 480 V 480 V 400 V
9 0x6075 (P323.00) Motor rated current 2,200 A 2,100 A 2,200 A 3,500 A
10 0x6073 (P324.00) Max current 200.0 % 150.0 % 200.0 % 200.0 %
Addional
funcons
Parameter change-over
Example: Selecve control of several motors with one inverter