EasyManua.ls Logo

Lenze i410 - Error Types

Lenze i410
334 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14.5.1 Error types
In the event of an error, the inverter response is determined by the error type dened for the
err
or.
Error type "No response"
The error is completely ignored (does not aect the running process).
Error type "Warning"
A warning does not severely aect the process and may be also ignored in consideraon of
safety aspects.
Error type "Fault"
The motor is brought to a standsll with the quick stop ramp.
The in
verter will only be disabled aer the quick stop is executed (motor at standsll) or
aer the
me-out me set in 0x2826 has been elapsed. 4Timeout for error response
^ 286
Excepon: In case of a serious fault, the inverter is disabled immediately. The motor has
no torque (coasts). For details see the table "Error codes, causes and remedies".
Error type "Trouble"
Just like "Fault", but the error state will be le automacally if the error condion is not acve
anymore.
Excepon: In case of a severe trouble, the inverter is disabled immediately. The motor has
no torque and coasts. For details see the table "Error codes, causes and remedies". ^ 290
The restart behavior aer trouble can be congured. 4
Automac restart aer a fault
^ 226
Comparison of the error types
The following table compares the main dierences of the error types:
Error type Logging in the Err
or
history buer /
Logbook
Inverter disable Motor stop Error reset is required "ERR" LED (red)
No response No No No No o
Warning Yes No No No
blinking fast (4 Hz)
Trouble Yes
aer quick stop or
immedia
tely.
quick stop ramp or
coasng.
No
blinking (1 Hz)
Fault Yes
For details see table "Err
or codes, causes and
remedies". ^ 290
Yes
on
Diagnoscs and fault eliminaon
Error handling
Err
or types
285

Table of Contents

Other manuals for Lenze i410

Related product manuals