14.5.1 Error types
In the event of an error, the inverter response is determined by the error type dened for the
err
or.
Error type "No response"
The error is completely ignored (does not aect the running process).
Error type "Warning"
A warning does not severely aect the process and may be also ignored in consideraon of
safety aspects.
Error type "Fault"
The motor is brought to a standsll with the quick stop ramp.
•
The in
verter will only be disabled aer the quick stop is executed (motor at standsll) or
aer the
me-out me set in 0x2826 has been elapsed. 4Timeout for error response
^ 286
•
Excepon: In case of a serious fault, the inverter is disabled immediately. The motor has
no torque (coasts). For details see the table "Error codes, causes and remedies".
Error type "Trouble"
Just like "Fault", but the error state will be le automacally if the error condion is not acve
anymore.
•
Excepon: In case of a severe trouble, the inverter is disabled immediately. The motor has
no torque and coasts. For details see the table "Error codes, causes and remedies". ^ 290
•
The restart behavior aer trouble can be congured. 4
Automac restart aer a fault
^ 226
Comparison of the error types
The following table compares the main dierences of the error types:
Error type Logging in the Err
or
history buer /
Logbook
Inverter disable Motor stop Error reset is required "ERR" LED (red)
No response No No No No o
Warning Yes No No No
blinking fast (4 Hz)
Trouble Yes
aer quick stop or
immedia
tely.
quick stop ramp or
coasng.
No
blinking (1 Hz)
Fault Yes
For details see table "Err
or codes, causes and
remedies". ^ 290
Yes
on
Diagnoscs and fault eliminaon
Error handling
Err
or types
285