9.5.2 Overcurrent monitoring
This funcon monitors the instantaneous value of the motor current and serves as motor
protecon.
WARNING!
With an incorrect
parameterisaon, the maximum permissible motor current may be
exceeded in the process.
Possible consequences: irreversible damage of the motor.
Avoid motor damages by using the overcurrent monitoring funcon as follows:
▶
The seng of the threshold for the overcurrent monitoring in 0x2D46:001 (P353.01) must
be adapted to the connected motor.
▶
Set the maximum output current of the inverter in 0x6073 (P324.00) much lower than the
threshold for overcurrent monitoring.
Details
The inverter monitors its output current. This monitoring is independent of the maximum
o
verload current
seng. 4Maximum overload current of the inverter^ 199
•
If the ins
tantaneous value of the motor current exceeds the threshold set in 0x2D46:001
(P353.01), the response set in 0x2D46:002 (P353.02) takes place.
•
With the seng 0x2D46:002
(P353.02) = "No response [0]", the monitoring funcon is
deacvated.
The threshold for the overcurrent monitoring is preset to four mes the rated motor current.
This preseng is overwrien in case a motor in the engineering tool is selected from the
"motor catalog" or the automac idencaon or calibraon of the motor data is carried out.
For a suitable protecon, the automacally adapted seng should be used. If disturbances
occur during operaon, the value can be increased.
Parameter
Address Name / seng range / [default seng] Informaon
0x2D46:001
(P353.01)
Overcurrent monitoring: Threshold
(Ov
ercurr. monit.: Threshold)
0.0 ... [6.8]* ... 1000.0 A
* Default seng dependent on the model.
•
From version 02.00
Warning/error threshold for overcurrent monitoring of the motor.
•
If the acve motor current exceeds the set threshold, the response
set in 0x2D46:002 (P353.02) is eected for the purpose of motor
protecon.
•
The par
ameter is calculated and set in the course of the automac
idencaon of the motor.
•
The par
ameter can also be set and overwrien by selecng a motor
from the "motor catalogue" of the engineering tool or performing an
automac calibraon of the motor.
4
Opons for opmizing the control loops ^ 175
0x2D46:002
(P353.02)
Overcurrent monitoring: Response
(Overcurr. monit.: Response)
Selecon of the response to the triggering of motor current monitoring.
Associated error code:
•
29056 | 0x7180 - Motor overcurrent
0 No response
4Err
or types ^ 285
1 Warning
2 Trouble
3 Fault
Conguring the motor control
Mot
or protecon
Overcurrent monitoring
194