6.2.5 Example: Jog forward/Jog reverse
This example shows the funcons "Jog forward (CW)" and "Jog reverse (CCW)" for Jog
operaon.
•
The s
witch S1 starts the motor in the forward direcon of rotaon. The switch S1 in the
inial
posion stops the motor again.
•
The buon S2 starts the motor in the forward direcon of rotaon with frequency preset
5.
•
The buon S3 starts the motor in the backward direcon of rotaon with frequency preset
6.
•
The motor rotates in jog operaon as long as the respecve buon is pressed. If both
buons are pressed at the same me, the motor is stopped.
CAUTION!
The jog operaon has a higher priority than the "Run" funcon, all other start commands and
the k
eypad key
.
If jog operaon is acve, the motor cannot be stopped with the previously menoned
funcons!
▶
The jog operaon is stopped by cancelling the funcons "Jog foward (CW)"/"Jog reverse
(CCW)".
▶
The jog operaon can be interrupted with the "Acvate quick stop" 0x2631:003
(P400.03)
funcon.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Buon S2 Jog foward (CW)
Buon S3 Jog reverse (CCW)
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Not connected [0]
0x2631:010 (P400.10) Jog foward (CW) Digital input 2 [12]
0x2631:011 (P400.11) Jog reverse (CCW) Digital input 3 [13]
0x2631:013 (P400.13) Reverse rotaonal direcon Not connected [0]
0x2911:005 (P450.05) Frequency setpoint presets: Preset 5 15 Hz (is used for jog forward)
0x2911:006 (P450.06) Frequency setpoint presets: Preset 6 10 Hz (is used for jog reverse)
Start, stop and rotang
direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands
Example: Jog forward/Jog reverse