7.2.4.1 Segment conguraon
Each step of a sequence can call a "segment". A segment contains, among other things preset
se
tpoints (speed setpoint, PID control value, torque setpoint), a combined acceleraon/
deceleraon for the speed setpoint and oponally a conguraon for the digital and analog
outputs.
Details
As a total, 8 segments and one end segment can be congured.
•
The sengs are only eecve if a sequence is acve and the respecve segment is
executed.
•
Only those sengs that are relevant for the corresponding operang mode must be made;
i.e. if the PID control is not used, no PID setpoint has to be set for the segment.
•
The following gure shows the segment sengs relevant for the operang mode 0x6060
(P301.00) = "MS: Velocity mode [-2]".
•
The table below provides a brief overview of the possible sengs of the dierent
segments.
Seng Info
Frequency setpoint
①
Only relevant for the
operang mode 0x6060 (P301.00) = "MS: Velocity mode [-2]". The direcon of
rotaon is implemented according to the sign.
Acceleraon/deceleraon
②
Only relevant for the operang mode 0x6060 (P301.00) = "MS: Velocity mode [-2]". The set me
refers to the acceleraon from standsll to the set maximum frequency. The deceleraon is eected
with the same ramp.
Time
③
Meaning for segment 1 ... 8:
Runme for the segment aer the expiraon of which a switchover to the next step of the sequence
occurs. Only relevant for the Sequencer mode 0x4025 (P800.00)Time operaon [1]" or "Time & step
operaon [3]".
④
Meaning for end segment:
Delay me for acvang the output states congured for the end segment.
Digital outputs
⑤
Oponally: Set digital outputs to a certain level for the execuon me of the segment.
Analog outputs
⑥
Oponally: Set analog outputs to an adjustable voltage value for the execuon me of the segment.
PID setpoint Only relevant if the PID control in 0x4020:001 (P600.01) is acvated.
4
Conguring the process controller ^ 98
Torque setpoint Only relevant for the operang mode 0x6060 (P301.00) = "MS: Torque mode [-1]".
4
Conguring the torque control ^ 129
In the following, all parameters relevant for the segment conguraon are given.
If the sequencer is
acve, write accesses to all parameters are blocked that
concern the acve segment conguraon!
Parameter
Address Name / seng range / [default seng] Informaon
0x4026:001
(P801.01)
Sequencer segment 1: Frequency setpoint
(Segment 1: Frequency setp.)
-599.0 ... [0.0] ... 599.0 Hz
•
From version 03.00
Frequency setpoint for the segment.
•
Only relevant for operang mode 0x6060 (P301.00) = "MS: Velocity
mode [-2]".
•
Direcon of rotaon according to sign.
Conguring the frequency control
Congure setpoint sources
Sequencer
75