9.5.3 Motor phase failure detecon
The motor phase failure detecon funcon can be acvated for asynchronous motors.
Precondions
Motor phase failure detecon during operaon is suitable for applicaons which are operated
with a c
onstant load and speed. In other cases, transient processes or unfavourable operang
points can cause erroneous triggering to occur.
Details
If a current-carrying motor phase (U, V, W) fails during operaon, the response selected in
0x2D45:001 (P310.01) is tripped and a logbook entry is made.
Excepon: With the seng "No response [0]", no logbook entry is made.
A motor phase failure can only be detected if
1.
the rated motor current is higher than 10 % of the rated inverter current and
2.
the output frequency is not lower than 0.1 Hz (standsll).
The lower the output frequency the longer the detecon of the motor phase failure.
Parameter
Address Name / seng range / [default seng] Informaon
0x2D45:001
(P310.01)
Motor phase failure detecon: Response - Motor
phase 1
(Mot.phase.
fail.: Response)
Selecon of the response following the detecon of a motor phase
failure during operaon.
Associated error codes:
65289 | 0xFF09 - Motor phase missing
65290 | 0xFF0A - Motor phase failure phase U
65291 | 0xFF0B - Motor phase failure phase V
65292 | 0xFF0C - Motor phase failure phase W
0 No response
4Err
or types ^ 285
1 Warning
2 Trouble
3 Fault
0x2D45:002
(P310.02)
Motor phase failure detecon: Current threshold
(Mot.phase.
fail.: Current thresh.)
1.0 ... [5.0] ... 25.0 %
Current threshold for the acvaon of the motor phase failure detecon
funcon.
100
% = Motor rated current 0x6075 (P323.00)
Display of the present motor current in 0x2D88 (P104.00).
0x2D45:003
(P310.03)
Motor phase failure detecon: Voltage threshold
(Mot.phase.
fail.: Voltage thresh.)
0.0 ... [10.0] ... 100.0 V
Voltage threshold for motor phase monitoring for the VFC control mode
(0x2C00 (P300.00) = 6).
The monitoring funcon is triggered if the motor current exceeds the
rated motor current-dependent current threshold for longer than
20 ms. Motor rated current 0x6075 (P323.00)
In case of the V/f characterisc control, the voltage threshold is
considered addionally for the motor phase failure detecon. If the
motor voltage is higher than the voltage threshold, monitoring is
combined with the motor current.
Conguring the motor control
Mot
or protecon
Motor phase failure detecon
195