9.5.3 Motor phase failure detecon
The motor phase failure detecon funcon can be acvated for asynchronous motors.
Precondions
Motor phase failure detecon during operaon is suitable for applicaons which are operated
with a c
onstant load and speed. In other cases, transient processes or unfavourable operang
points can cause erroneous triggering to occur.
Details
If a current-carrying motor phase (U, V, W) fails during operaon, the response selected in
0x2D45:001 (P310.01) is tripped and a logbook entry is made.
Excepon: With the seng "No response [0]", no logbook entry is made.
A motor phase failure can only be detected if
1.
the rated motor current is higher than 10 % of the rated inverter current and
2.
the output frequency is not lower than 0.1 Hz (standsll).
The lower the output frequency the longer the detecon of the motor phase failure.
Parameter
Address Name / seng range / [default seng] Informaon
0x2D45:001
(P310.01)
Motor phase failure detecon: Response - Motor
phase 1
(Mot.phase.
fail.: Response)
Selecon of the response following the detecon of a motor phase
failure during operaon.
Associated error codes:
•
65289 | 0xFF09 - Motor phase missing
•
65290 | 0xFF0A - Motor phase failure phase U
•
65291 | 0xFF0B - Motor phase failure phase V
•
65292 | 0xFF0C - Motor phase failure phase W
0 No response
4Err
or types ^ 285
1 Warning
2 Trouble
3 Fault
0x2D45:002
(P310.02)
Motor phase failure detecon: Current threshold
(Mot.phase.
fail.: Current thresh.)
1.0 ... [5.0] ... 25.0 %
Current threshold for the acvaon of the motor phase failure detecon
funcon.
•
100
% = Motor rated current 0x6075 (P323.00)
•
Display of the present motor current in 0x2D88 (P104.00).
0x2D45:003
(P310.03)
Motor phase failure detecon: Voltage threshold
(Mot.phase.
fail.: Voltage thresh.)
0.0 ... [10.0] ... 100.0 V
Voltage threshold for motor phase monitoring for the VFC control mode
(0x2C00 (P300.00) = 6).
•
The monitoring funcon is triggered if the motor current exceeds the
rated motor current-dependent current threshold for longer than
20 ms. Motor rated current 0x6075 (P323.00)
•
In case of the V/f characterisc control, the voltage threshold is
considered addionally for the motor phase failure detecon. If the
motor voltage is higher than the voltage threshold, monitoring is
combined with the motor current.
Conguring the motor control
Mot
or protecon
Motor phase failure detecon
195