9.4.6.7 Flying restart controller
For a quick commissioning, the calculaons and sengs are made automacally during the
mot
or calibraon.
Details
The following parameter is only relevant for the ying restart circuit if an asynchronous motor
is controlled.
Parameter
Address Name / seng range / [default seng] Informaon
0x2BA1:003
(P718.03)
Flying restart circuit: Restart
me
(Flying restart: Restart me)
1 ... [5911]* ... 60000 ms
* Default seng dependent on the model.
Integraon me for controlling the ying restart circuit.
9.4.6.8 SLVC controller
For a quick commissioning, the calculaons and sengs are made automacally during the
mot
or calibraon.
Precondions
The SLVC controller is only eecve in the motor control type "Sensorless vector control
(SLVC)".
Parameter
Address Name / seng range / [default seng] Informaon
0x2B40:001 Gain
0.0000 ... [0.2686]* ... 1000.0000 Hz/
A
* Default seng dependent on the model.
Gain of the SLVC-Q controller.
0x2B40:002 Reset me
1.0 ... [2.3]* ... 2000.0 ms
* Default seng dependent on the model.
Reset me of the SLVC-Q controller.
Conguring the motor control
Opons for opmizing the control loops
Mot
or control sengs
188