4.4 General
informaon on parameter seng
As a part of a machine with a speed-variable drive system, the inverter must be adapted to its
drive task. The adaptaon process of the inverter is carried out by changing parameters.
These parameters can be accessed by means of the keypad or »EASY Starter«. If the inverter is
provided with a network opon, access can also be eected by a higher-level controller via
the corresponding network.
Certain device commands or sengs which might cause a crical state of the
driv
e behavior can only be carried out when the device is disabled.
4.4.1 Addressing of the parameters
Each parameter features a 16-bit index as its address. Under this address, the parameter is
s
tored in the object directory of the device.
•
P
arameters that belong together funconally are combined in a data set. These
par
ameters are addionally provided with an 8-bit subindex.
•
The colon is used as a separator between the index and subindex Example: "0x2540:001"
•
There are parameter sengs that can be changed, and (diagnosc) parameters that can
only be read.
Parameterisaon using the keypad
•
All par
ameters which can also be accessed by means of the keypad have a "Display code",
with the rst digit of the display code specifying the group in which the parameter can be
f
ound on the keypad.
•
In the documentaon, the display code is specied in brackets behind the address.
Example: "0x2915 (P210.00)".
Commissioning
Gener
al informaon on parameter seng
Addressing of the parameters
22