Address Name / seng range / [default seng] Informaon
0x2631:011
(P400.11)
Funcon list: Jog reverse (CCW)
(Funcon list: Jog reverse)
•
Seng can only be changed if the inverter is
disabled.
•
F
or further possible sengs, see parameter
0x2631:010 (P400.10). ^ 50
Assignment of a trigger for the "Jog reverse (CCW)" funcon.
Trigger = TRUE: Let motor rotate backward with preset 6.
Trigger = FALSE: Stop motor.
CAUTION! The jog operaon has a higher priority than the "Run"
funcon, all other start commands and the keypad key .
•
If jog operaon is acve, the motor cannot be stopped with the
pr
eviously menoned funcons!
•
Ho
wever, jog operaon can be interrupted by the "Quick stop"
funcon.
Notes:
•
The pr
eset 6 can be set in 0x2911:006 (P450.06).
•
The stop method can be selected in 0x2838:003 (P203.03).
•
If "Jog foward (CW)" and "Jog reverse (CCW)" are acvated at the
same me, the motor is stopped using the set stop method and jog
operaon must be triggered again.
•
Jog operaon cannot be started automacally. The "Start at power-
up" opon in 0x2838:002 (P203.02) does not apply to jog operaon.
4Ex
ample: Jog forward/Jog reverse^ 57
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:013
(P400.13)
Funcon list: Reverse rotaonal direcon
(Funcon list: Reverse rot.dir.)
•
Seng can only be changed if the inverter is
disabled.
•
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the "Reverse rotaonal direcon"
funcon.
Trigger = TRUE: the setpoint specied is inverted (i. e. the sign is
inverted).
Trigger = FALSE: no acon / deacvate funcon again.
4Example: Start/stop (1 signal) and reversal^ 54
13 Digital input 3 State of X3/DI3, taking an inversion set in 0x2632:003
(P411.03) into
consideraon.
6.2.1 Trigger list
The trigger list lists all selecon opons (triggers) for the funcons which can be congured
using the parameters 0x2631:xx (P400.xx).
Selecon Informaon
0 Not connected No trigger assigned (trigger is constantly FALSE).
1 Constant TRUE Trigger is constantly TRUE.
11 Digital input 1 State of X3/DI1, taking an inversion set in 0x2632:001
(P411.01) into
consideraon.
12 Digital input 2 State of X3/DI2, taking an inversion set in 0x2632:002 (P411.02) into
consideraon.
13 Digital input 3 State of X3/DI3, taking an inversion set in 0x2632:003 (P411.03) into
consideraon.
14 Digital input 4 State of X3/DI4, taking an inversion set in 0x2632:004 (P411.04) into
consideraon.
15 Digital input 5 State of X3/DI5, taking an inversion set in 0x2632:005 (P411.05) into
consideraon.
50 Running TRUE if inverter and start are enabled and output frequency > 0 Hz.
Otherwise FALSE.
Excepon, quick stop mode: TRUE if inverter and start are enabled and
output frequency > 0.2 Hz. Otherwise FALSE.
51 Ready for operaon TRUE if inverter is ready for operaon (no error acve, no STO acve and
DC-bus voltage ok). Otherwise FALSE.
TRUE, wenn Inverter betriebsbereit (kein Fehler akv und
Zwischenkreisspannung ok). Sonst FALSE.
53 Stop acve TRUE if inverter is enabled and motor is not started and output
fr
equency = 0.
54 Quick stop acve TRUE if quick stop is acve. Otherwise FALSE.
58 Device warning acve TRUE if warning is acve. Otherwise FALSE.
•
A w
arning has no impact on the operang status of the inverter.
•
A warning is reset automacally if the cause has been eliminated.
Start, stop and rotang
direcon commands
Flexible I/O conguraon of the start, stop and rotang direcon commands
Trigger list